Key

2178

Conference Year

2012

Keywords

evaporartor, maldistribution, compensation, modeling, Modelica

Abstract

Compensation of airflow maldistribution in fin-and tube evaporators for residential air-conditioning is investigated with regards to circuitry design and control of individual channel superheats. In particularly, the interlaced and the face split circuitry designs are compared numerically using a linear velocity profile and a CFD predicted velocity profile obtained from Kærn (2011d) in dry and wet conditions. The circuitry models are validated experimentally in wet conditions, and for this purpose a test case interlaced evaporator (17.58 kW) was reconstructed in order to become a face split evaporator by modifying its U-bend connections. Furthermore, a 14% and 28% blockage of the face split evaporator is studied experimentally with control of individual channel superheats. It is shown that the face split circuitry with compensation gives the best performance in both dry and wet conditions, however with lower gains in wet conditions (around 3% in cooling capacity and 7-9% in UA-value). This performance gain in cooling capacity is below the uncertainty in standard experiments, however the gain may be revealed and/or validated by the possible area savings experimentally, i.e. in terms of overall UA-value.